Product reference standard

GB / t15576-2008 low voltage complete reactive power compensation device

DL / t597-1996 technical specification for ordering low voltage reactive power compensation controller

JB / t9663-2013 low voltage reactive power automatic compensation controller


Environment condition

Ambient temperature: - 25 ℃~ 70 ℃ in operation, - 40 ℃~ 85 ℃ in transportation and storage

Relative humidity: 20% ~ 90% at 40 ℃

Atmospheric pressure: 79.5-106kpa (altitude 2500m and below)


Working voltage of power supply

220 V ± 20%; frequency 50 Hz ± 5%; total distortion rate of sine wave ≤ 5%


Measurement accuracy 

Voltage analog (10% - 100% maximum): 0.5 level

Current analog (1% - 100% max): 0.5 level

When the phase angle ∮ is between - 30 ° and + 60 °, the power level is 0.5 and the power factor level is 0.5


Switching mode

Switching mode: intelligent analysis switching (connected capacitors can be arranged arbitrarily)


Parameter description

Threshold: 0.5-1, default: 0.95; cut threshold: 1~-0.50; default: 1.0

Setting range of current ratio: 1-2999, factory default: 0500

Over voltage setting range: 240-269v, factory default: 259v

Under voltage setting range: 170-199v, factory default: 190V

Delay range of switch analysis: dynamic / static: 0-99s, default: 15s (0.2S in 0s)

Fast: 0-9.9s, default: 0.04s (0.04s in 0s)

The setting range of harmonic protection: 0.0% - 90%, and the harmonic protection function will be turned off if the setting is more than 90%, and the default value is off.


File Download:JKWF series instruction.pdf


The address of this article:http://www.diandq.com/en/product/549.html

Key word:Controllervoltage,Controllerdescription,Controlleraccuracy

Recently browse:

Telephone number: (+ 86) - 0750-6122405 (+ 86) - 0750-6126137 (+ 86) - 0750-6131503

Fax No. (+ 86) - 0750-6131898

Hotline: Miss Zhou 18948962956, Mr. Zhong 13825500653

E-mail: lijiugosi@163.com

Address: No.1 Jinshun Road, East District, Jinguzhou Development Zone, Xinhui District, Jiangmen City, Guangdong Province

Postal Code: 529100

Copyright © http://www.diandq.com/en/ Guangdong Dian Electric Technology Co., Ltd Specializing in Power capacitor manufacturer,Manufacturer of reactive power compensation controller,Composite switch manufacturer ,Welcome to inquire!
粤ICP备18104981号   Powered by Clouds platform   Technical Support: 华企立方